OutBack

OUTBACK BATTERY INVERTER

  • Sale
  • $1,854.23


The new OutBack VFX series is a ventilated version of our original sealed FX series modular "building block” sine wave inverter/charger that can be used for both small and large power systems. By allowing cooler outside airflow through the internal electronics, more AC power is available and operation in extremely hot environments is improved compared to the sealed FX series. Each OutBack FX or VFX inverter/charger is a complete power conversion system - DC to AC inverter, battery charger and AC transfer switch. Additional FX inverter/chargers can be connected at any time in either parallel (120 VAC), series (120/240 VAC), or three-phase (120Y208 VAC) configurations. This allows a system to be tailored to meet the specific power conversion requirements of the application, both at the time of the installation and in the future. The OutBack VFX series is also available in export versions (E)with 230 VAC, 50 hz output that can be connected in parallel (230 VAC) or in three phase (230Y400 VAC) configurations. Like the FX series, the OutBack VFX is also designed to survive harsh environments around the world. The full sreened vent openings are "bug-proof" and the die-cast aluminum chassis protects and keeps the power conversion components cool in very hot environments even when operated at high power for extended periods. The VFX can be used in high ambient applications up to 60oC (with reduced output ratings). The OutBack VFX series inverter/charger system is designed for both residential and commercial stand-alone or back-up power applications with battery energy storage. It is designed to operate as a coordinated system with the other OutBack products i.e. the PSDC, PSAC and PSR enclosures as well as the MX60 MPPT charge controllers and MATE system controller and display.

 

Item code Model number Volts Watts Waveform
OUTVFX3524 VFX3524 24V 3500W Pure

 

VFX 3524  VFX 3648 
Continuous Power Rating at 25 degrees C 2600VA 2800VA 3000VA 3000VA 3000VA 3500VA 3600VA
Nominal DC Input Voltage 12 12 24 24 48 24 48
Nominal AC Input Voltage / Frequency 230V/50Hz 120V/60Hz 230V/50Hz 120V/50Hz 230V/50Hz 120V/60Hz 120V/60Hz
Continuous AC RMS Output current at 25 C 11.4 amps 23.3 amps 13 amps 13 amps 13 amps 29.2 amps 30 amps
Idle Power (typical at no AC load) (sleep – 3 watts) 18-20 Watts 19-21 Watts 18-20 Watts 18-20 Watts 21-23 Watts 18-20 Watts 21-23 Watts
Efficiency (typical at 25 degree C and 75% resistive load) 90% >90% 92% 92% 93% >90% >90%
Total Harmonic distortion voltage (typical / max) 2% / 5% 2% / 5% 2% / 5% 2% / 5% 2% / 5% 2% / 5% 2% / 5%
Output Voltage Regulation +/- 2% typ +/- 2% typ +/- 2% typ +/- 2% typ +/- 2% typ +/- 2% typ +/- 2% typ
Surge Power Capability Peak (1mSec) 28 amps AC 70 amps AC 35 amps AC 35 amps AC 35 amps AC 70 amps AC 70 amps AC
Surge Power Capability RMS (100mSec) 25 amps AC 50 amps AC 25 amps AC 25 amps AC 25 amps AC 50 amps AC 50 amps AC
Overload Capability (from 25 C start) 5second 4000 VA 4800 VA 4800 VA 4800 VA 4800 VA 5000 VA 5000 VA
Overload Capability (from 25 C start) 30 minutes 3100 VA 3200 VA 3300 VA 3300 VA 3300 VA 4000 VA 4000 VA
Automatic AC transfer Relay (at nominal AC) 30 amps AC 60 amps AC 30 amps AC 30 amps AC 30 amps AC 60 amps AC 60 amps AC
AC Input Current (adjustable limits) 30 amps AC 60 amps max 30 amps max 30 amps max 30 amps max 60 amps max 60 amps max
AC Input Voltage Range (adjustable limits) 160-300 VAC 90-140VAC 160-300 VAC 160-300 VAC 160-300 VAC 90-140VAC 90-140VAC
Frequency Range – AC Input 44 to 56 Hz 54-67.4 Hz 44 to 56 Hz 44 to 56 Hz 44 to 56 Hz 54-67.4 Hz 54-67.4 Hz
DC Input Range (adjustable low battery cut-out) 10.5 – 17 VDC 10-16 VDC 21-34 VDC 21-34 VDC 42-68 VDC 20-33 VDC 40-66 VDC
Recommended DC Breaker OBDC-250 OBDC-250 OBDC-250 OBDC-250 OBDC-175 OBDC-250 OBDC-175
Continuous Battery Charger Output amps DC 120A 125A 85A 85A 45A 85A 45A
Shipping Weight 62 Lbs 62 Lbs 62 Lbs 62 Lbs 62 Lbs 62 Lbs 62 Lbs